Your advantages- Possible to connect up to 20 safety switches in series
- Integrated short circuit monitoring by pulsing
- Large operating distance
- High protection against tampering
- Adjustable actuating head with 5 approach directions (only housing C01)
- Fastenings compatible with standard housing according to EN 60947-5-2(only housing C01)
- Fastenings compatible with standard housing
- Diagnostics using LED
The non-contact safety switch CES-AR-… is designed for systems in which a large number of safety doors need to be monitored. It can also be used as a compact individual switch. The small design of the actuator and switch makes mounting on the safety guard easy. Design and functionalityThe safety switches are connected together using connectors. The CES-AR-... has two safety outputs. In a chain of switches, the signals from the safety outputs are connected to the next switch. The outputs on the last switch in the chain are connected directly to drives, downstream safety relays or safe control systems. The switch monitors itself for short circuits using pulsed signals. External clock signals are not allowed (see next section). |  |  | more information |
Indication for actuator in the boundary areaIf the safety door with the actuator should settle over time, the actuator can drift out of the read head operating distance. The device recognizes this and indicates that the actuator is in the boundary area (function available from V 1.1.2 and higher). This allows the safety door to be readjusted in time. Connection to safe control systems or safety relaysDo not use a control system or safety relay with pulsing for monitoring short circuits or switch off the pulsing function in these devices. The switch generates its own clock signals on the output lines OA/OB. A downstream device must tolerate these test pulses, which may have a length of up to 1ms. The inputs on the downstream device must be suitable for positive-switching devices (pnp outputs), as the two outputs on the safety switch deliver a level of +24 V in the switched-on state. OUT outputThe semiconductor output OUT is switched if the safety guard is closed (actuator in the operating distance). It is not allowed to be used for safety functions. The OUT outputs on the individual switches can, however, not be polled if connected in series using a Y-distributor. Evaluation is only possible on parallel wiring to the control cabinet. RST inputThe switches in a chain in a fault state can be reset using the RST input. To do this, a voltage of 24 V is applied to the RST input for at least 3 seconds. It is not necessary to disconnect the supply of power to reset a fault. Usage as individual switch or switch chainThe safety switch CES-AR can be operated as a compact individual switch or in a switch chain with max. 20 devices. If a single CES-AR is used, connect the switch as shown in figure above. The OUT output can also be connected here to a control system as a monitoring output. The switches are connected in series using plug connectors and Y-distributors. The first switch in the chain must always be fitted with a bridging plug. If a safety guard is opened or if a fault occurs on one of the switches, the system shuts down the machine. A higher level control system can, however, not detect which safety guard is open or on which switch a fault has occurred. A special AR evaluation unit is required. |
 | Non-contact safety switch CES-AR-C01... |
- Read head with integrated evaluation electronics
- Up to 20 switches in series
- Short circuit monitoring
- 2 safety outputs (semiconductor outputs)
- Category 4 / PL e according to EN ISO 13849-1
Approach directionCan be adjusted in 90° steps Short circuit monitoringThe switch generates its own clock signal on the output cables OA/OB. Pay attention to this aspect when connecting to control systems and relays. Unicode evaluationEach actuator is unique. The safety switch detects only the actuator that has been taught-in. Additional actuators can be taught-in.
Only the last actuator taught-in is detected. Multicode evaluationEvery suitable actuator is detected by the safety switch. Fixcode evaluationAn actuator CES-A-BPA is permanently allocated to the evaluation unit. The evaluation unit can be operated only with this actuator. The actuator is taught-in at EUCHNER prior to delivery. No additional actuators can be taught-in. Category according to EN 13849-1Due to two redundant design semiconductor outputs (safety outputs) with internal monitoring suitable for: - Category 4 /PL e according to EN 13849-1
Important: To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated. LED indicator| STATE | Status LED | | DIA | Diagnostics LED |
Additional connections| OUT | Monitoring output (semiconductor) | | RST | Reset input |
Important:Only safety switches CES-AR-C01 from serial number V 1.1.2 can be connected to the AR evaluation unit. Order numbers:Unicode Multicode Fixcode (actuator CES-A-BPA included) | Non-contact safety switch CES-AR-C01... M12 plug, 8-pin Block diagram Terminal assignment (View of connection side of the safety switch)  |
 | Non-contact safety switch CES-AR-CR2-... , plug connector M8 |
- Read head with integrated evaluation electronics
- Up to 20 switches in series
- Short circuit monitoring
- 2 safety outputs (semiconductor outputs)
- Door hinge right
- Category 4/PL e according to EN ISO 13849-1
- With plug connector M8, 8-pin
Short circuit monitoring
The switch generates its own clock signal on the output cables OA/OB.
Pay attention to this aspect when connecting to control systems and relays.
Unicode evaluation
Each actuator is unique. The safety switch detects only the actuator that has been taught-in. Additional actuators can be taught-in. Only the last actuator taught-in is detected.
Multicode evaluation
Every suitable actuator is detected by the evaluation unit.
Category according to EN 13849-1
Due to two redundant design semiconductor outputs (safety outputs) with internal monitoring suitable for:
- Category 4 /PL e according to EN 13849-1
Important: To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.
LED indicator
| STATE | Status LED | | DIA | Diagnostics LED |
Additional connections
| OUT | Monitoring output (semiconductor) | | RST | Reset input |
Important:Only safety switches CES-AR-CR2 from serial number V 1.1.2 can be connected to the AR evaluation unit.
Approach directions
Order numbers:Unicode - 105 751 CES-AR-CR2-AH-SG-105751
Multicode - 105 750 CES-AR-CR2-CH-SG-105750
| Non-contact safety switch CES-AR-CR2-... |
 | Non-contact safety switch CES-AR-CL2-... , plug connector M8 |
- Read head with integrated evaluation electronics
- Up to 20 switches in series
- Short circuit monitoring
- 2 safety outputs (semiconductor outputs)
- Door hinge left
- Category 4/PL e according to EN ISO 13849-1
- With plug connector M8, 8-pin
Short circuit monitoring
The switch generates its own clock signal on the output cables OA/OB.
Pay attention to this aspect when connecting to control systems and relays.
Unicode evaluation
Each actuator is unique. The evaluation unit detects only the actuator that has been taught-in. Additional actuators can be taught-in. Only the last actuator taught-in is detected.
Multicode evaluation
Every suitable actuator is detected by the evaluation unit.
Category according to EN 13849-1
Due to two redundant design semiconductor outputs (safety outputs) with internal monitoring suitable for:
- Category 4 /PL e according to EN 13849-1
Important:To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.
LED indicator
| STATE | Status LED | | DIA | Diagnostics LED |
Additional connections
| OUT | Monitoring output (semiconductor) | | RST | Reset input |
Important:Only safety switches CES-AR-CL2 from serial number V 1.1.2 can be connected to the AR evaluation unit.
Approach directions
Order numbers:Unicode - 105 753 CES-AR-CL2-AH-SG-105753
Multicode - 105 752 CES-AR-CL2-CH-SG-105752
| Non-contact safety switch CES-AR-CL2-... |
 | Non-contact safety switch CES-AR-CR2-... , plug connector M12, PUR |
- Read head with integrated evaluation electronics
- Up to 20 switches in series
- Short circuit monitoring
- 2 safety outputs (semiconductor outputs)
- Door hinge right
- Category 4/PL e according to EN ISO 13849-1
- Connection cable PUR
- With plug connector M12, 8-pin
Short circuit monitoring
The switch generates its own clock signal on the output cables OA/OB.
Pay attention to this aspect when connecting to control systems and relays.
Unicode evaluation
Each actuator is unique. The evaluation unit detects only the actuator that has been taught-in. Additional actuators can be taught-in. Only the last actuator taught-in is detected.
Multicode evaluation
Every suitable actuator is detected by the evaluation unit.
Category according to EN 13849-1
Due to two redundant design semiconductor outputs (safety outputs) with internal monitoring suitable for:
- Category 4 /PL e according to EN 13849-1
Important:To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.
LED indicator
| STATE | Status LED | | DIA | Diagnostics LED |
Additional connections
| OUT | Monitoring output (semiconductor) | | RST | Reset input |
Important:Only safety switches CES-AR-CR2 from version number V 1.1.2 can be connected to the AR evaluation unit.
Approach directions
Order numbers:Unicode - 105 746 CES-AR-CR2-AH-SA-105746
Multicode - 105 745 CES-AR-CR2-CH-SA-105745
| Non-contact safety switch CES-AR-CR2-... |
 | Non-contact safety switch CES-AR-CL2-... , plug connector M12, PUR |
- Read head with integrated evaluation electronics
- Up to 20 switches in series
- Short circuit monitoring
- 2 safety outputs (semiconductor outputs)
- Door hinge left
- Category 4/PL e according to EN ISO 13849-1
- Connection cable PUR
- With plug connector M12, 8-pin
Short circuit monitoring
The switch generates its own clock signal on the output cables OA/OB.
Pay attention to this aspect when connecting to control systems and relays.
Unicode evaluation
Each actuator is unique. The evaluation unit detects only the actuator that has been taught-in. Additional actuators can be taught-in. Only the last actuator taught-in is detected.
Multicode evaluation
Every suitable actuator is detected by the evaluation unit.
Category according to EN 13849-1
Due to two redundant design semiconductor outputs (safety outputs) with internal monitoring suitable for:
- Category 4 /PL e according to EN 13849-1
Important:To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.
LED indicator
| STATE | Status LED | | DIA | Diagnostics LED |
Additional connections
| OUT | Monitoring output (semiconductor) | | RST | Reset input |
Important:Only safety switches CES-AR-CL2 from serial number V 1.1.2 can be connected to the AR evaluation unit.
Approach directions
Order numbers:Unicode - 105 748 CES-AR-CL2-AH-SA-105748
Multicode - 105 747 CES-AR-CL2-CH-SA-105747
| Non-contact safety switch CES-AR-CL2-... |
 | Non-contact safety switch CES-AR-CR2-..., with flying lead, PUR |
- Read head with integrated evaluation electronics
- Up to 20 switches in series
- Short circuit monitoring
- 2 safety outputs (semiconductor outputs)
- Door hinge right
- Category 4/PL e according to EN ISO 13849-1
- With flying lead
- Connection cable PUR
Short circuit monitoring
The switch generates its own clock signal on the output cables OA/OB.
Pay attention to this aspect when connecting to control systems and relays.
Unicode evaluation
Each actuator is unique. The evaluation unit detects only the actuator that has been taught-in. Additional actuators can be taught-in. Only the last actuator taught-in is detected.
Multicode evaluation
Every suitable actuator is detected by the evaluation unit.
Category according to EN 13849-1
Due to two redundant design semiconductor outputs (safety outputs) with internal monitoring suitable for:
- Category 4 /PL e according to EN 13849-1
Important: To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.
LED indicator
| STATE | Status LED | | DIA | Diagnostics LED |
Additional connections
| OUT | Monitoring output (semiconductor) | | RST | Reset input |
Important:Only safety switches CES-AR-CL2 from serial number V 1.1.2 can be connected to the AR evaluation unit.
Approach directions
Order numbers:Unicode - 109 046 CES-AR-CR2-AH-L05-109046
- 109 050 CES-AR-CR2-AH-L10-109050
- 109 054 CES-AR-CR2-AH-L20-109054
Multicode - 109 044 CES-AR-CR2-CH-L05-109044
- 109 048 CES-AR-CR2-CH-L10-109048
- 109 052 CES-AR-CR2-CH-L20-109052
| Non-contact safety switch CES-AR-CR2-... |
 | Non-contact safety switch CES-AR-CL2-..., with flying lead, PUR |
- Read head with integrated evaluation electronics
- Up to 20 switches in series
- Short circuit monitoring
- 2 safety outputs (semiconductor outputs)
- Door hinge left
- Category 4/PL e according to EN ISO 13849-1
- With flying lead
- Connection cable PUR
Short circuit monitoring
The switch generates its own clock signal on the output cables OA/OB.
Pay attention to this aspect when connecting to control systems and relays.
Unicode evaluation
Each actuator is unique. The evaluation unit detects only the actuator that has been taught-in. Additional actuators can be taught-in. Only the last actuator taught-in is detected.
Multicode evaluation
Every suitable actuator is detected by the evaluation unit.
Category according to EN 13849-1
Due to two redundant design semiconductor outputs (safety outputs) with internal monitoring suitable for:
- Category 4 /PL e according to EN 13849-1
Important: To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.
LED indicator
| STATE | Status LED | | DIA | Diagnostics LED |
Additional connections
| OUT | Monitoring output (semiconductor) | | RST | Reset input |
Important:Only safety switches CES-AR-CL2 from serial number V 1.1.2 can be connected to the AR evaluation unit.
Approach directions
Order numbers:Unicode - 109 047 CES-AR-CL2-AH-L05-109047
- 109 051 CES-AR-CL2-AH-L10-109051
- 109 055 CES-AR-CL2-AH-L20-109055
Multicode - 109 045 CES-AR-CL2-CH-L05-109045
- 109 049 CES-AR-CL2-CH-L10-109049
- 109 053 CES-AR-CL2-CH-L20-109053
| Non-contact safety switch CES-AR-CL2-... |
Click on the product to view the available accessories!  | Non-contact safety switch CES-AR-C01... |
Actuator - Actuator CES-A-BBA
- Actuator CES-A-BCA
- Actuator CES-A-BPA
- Actuator CES-A-BRN
Bolt - Bolt CES-A-C
- Bolt CES-A-C/F with escape release
Connection material - Connection cables with plug connector M12 for safety switch CES-AR/CET-AR/CES-AP-C01
100 177 C-M12F08-08X025PV05,0-MA-100177100 178 C-M12F08-08X025PV10,0-MA-100178100 179 C-M12F08-08X025PV20,0-MA-100179 - Connection cables with 2 plug connectors M12 for safety switch CES-AR/CET-AR
100 180 C-M12F05-05X034PV05,0-M12M05-100180100 181 C-M12F05-05X034PV10,0-M12M05-100181100 182 C-M12F05-05X034PV20,0-M12M05-100182 - Connection cables with plug connector M12 for safety switch CES-AR/CET-AR/CES-AP/CES-FD
100 183 C-M12F05-05X034PV05,0-MA-100183100 184 C-M12F05-05X034PV10,0-MA-100184100 185 C-M12F05-05X034PV20,0-MA-100185 - Connection cables with female plug M8 and flying lead for CES-AR-C.2
106 671 C-M08F08-08X014PU05,0-ES-106671106 672 C-M08F08-08X014PU10,0-ES-106672106 673 C-M08F08-08X014PU20,0-ES-106673 - Bridging plug M12
- Y-distributor M12
097 627 Y-distributor M12
 | Non-contact safety switch CES-AR-CR2-... , plug connector M8 |
Actuator - Actuator CES-A-BLN-R...
100 776 CES-A-BLN-R2-100776 - Actuator CES-A-BLN-U...
103 450 CES-A-BLN-U2-103450 - Actuator CES-A-BDN-06
104 730 CES-A-BDN-06-104730
Connection material - Bridging plug M12
- Y-distributor M12
097 627 Y-distributor M12 - Connection cables with female plug M8 and flying lead for CES-AR-C.2
106 671 C-M08F08-08X014PU05,0-ES-106671106 672 C-M08F08-08X014PU10,0-ES-106672106 673 C-M08F08-08X014PU20,0-ES-106673110 933 C-M08F08-08X014PV205,0-ES-110933110 934 C-M08F08-08X014PV210,0-ES-110934110 935 C-M08F08-08X014PV210,0-ES-110935111 603 C-M08F08-08X014PV220,0-ES-111603
Evaluation Unit - AR evaluation unit CES-AR-AES-12
 | Non-contact safety switch CES-AR-CL2-... , plug connector M8 |
Actuator - Actuator CES-A-BLN-L...
104 510 CES-A-BLN-L2-104510 - Actuator CES-A-BLN-U...
103 450 CES-A-BLN-U2-103450 - Actuator CES-A-BDN-06
104 730 CES-A-BDN-06-104730
Connection material - Bridging plug M12
- Y-distributor M12
097 627 Y-distributor M12 - Connection cables with female plug M8 and flying lead for CES-AR-C.2
106 671 C-M08F08-08X014PU05,0-ES-106671106 672 C-M08F08-08X014PU10,0-ES-106672106 673 C-M08F08-08X014PU20,0-ES-106673110 933 C-M08F08-08X014PV205,0-ES-110933110 934 C-M08F08-08X014PV210,0-ES-110934110 935 C-M08F08-08X014PV210,0-ES-110935111 603 C-M08F08-08X014PV220,0-ES-111603
Evaluation Unit - AR evaluation unit CES-AR-AES-12
 | Non-contact safety switch CES-AR-CR2-... , plug connector M12, PUR |
Actuator - Actuator CES-A-BLN-R...
100 776 CES-A-BLN-R2-100776 - Actuator CES-A-BLN-U...
103 450 CES-A-BLN-U2-103450 - Actuator CES-A-BDN-06
104 730 CES-A-BDN-06-104730
Connection material - Connection cables with plug connector M12 for safety switch CES-AR/CET-AR/CES-AP-C01
100 177 C-M12F08-08X025PV05,0-MA-100177100 178 C-M12F08-08X025PV10,0-MA-100178100 179 C-M12F08-08X025PV20,0-MA-100179 - Connection cables with 2 plug connectors M12 for safety switch CES-AR/CET-AR
100 180 C-M12F05-05X034PV05,0-M12M05-100180100 181 C-M12F05-05X034PV10,0-M12M05-100181100 182 C-M12F05-05X034PV20,0-M12M05-100182 - Connection cables with plug connector M12 for safety switch CES-AR/CET-AR/CES-AP/CES-FD
100 183 C-M12F05-05X034PV05,0-MA-100183100 184 C-M12F05-05X034PV10,0-MA-100184100 185 C-M12F05-05X034PV20,0-MA-100185 - Bridging plug M12
- Y-distributor M12
097 627 Y-distributor M12
Evaluation Unit - AR evaluation unit CES-AR-AES-12
 | Non-contact safety switch CES-AR-CL2-... , plug connector M12, PUR |
Actuator - Actuator CES-A-BLN-L...
104 510 CES-A-BLN-L2-104510 - Actuator CES-A-BLN-U...
103 450 CES-A-BLN-U2-103450 - Actuator CES-A-BDN-06
104 730 CES-A-BDN-06-104730
Connection material - Connection cables with plug connector M12 for safety switch CES-AR/CET-AR/CES-AP-C01
100 177 C-M12F08-08X025PV05,0-MA-100177100 178 C-M12F08-08X025PV10,0-MA-100178100 179 C-M12F08-08X025PV20,0-MA-100179 - Connection cables with 2 plug connectors M12 for safety switch CES-AR/CET-AR
100 180 C-M12F05-05X034PV05,0-M12M05-100180100 181 C-M12F05-05X034PV10,0-M12M05-100181100 182 C-M12F05-05X034PV20,0-M12M05-100182 - Connection cables with plug connector M12 for safety switch CES-AR/CET-AR/CES-AP/CES-FD
100 183 C-M12F05-05X034PV05,0-MA-100183100 184 C-M12F05-05X034PV10,0-MA-100184100 185 C-M12F05-05X034PV20,0-MA-100185 - Bridging plug M12
- Y-distributor M12
097 627 Y-distributor M12
Evaluation Unit - AR evaluation unit CES-AR-AES-12
 | Non-contact safety switch CES-AR-CR2-..., with flying lead, PUR |
Actuator - Actuator CES-A-BLN-R...
100 776 CES-A-BLN-R2-100776 - Actuator CES-A-BLN-U...
103 450 CES-A-BLN-U2-103450 - Actuator CES-A-BDN-06
104 730 CES-A-BDN-06-104730
Evaluation Unit - AR evaluation unit CES-AR-AES-12
 | Non-contact safety switch CES-AR-CL2-..., with flying lead, PUR |
Actuator - Actuator CES-A-BLN-L...
104 510 CES-A-BLN-L2-104510 - Actuator CES-A-BLN-U...
103 450 CES-A-BLN-U2-103450 - Actuator CES-A-BDN-06
104 730 CES-A-BDN-06-104730
Evaluation Unit - AR evaluation unit CES-AR-AES-12
 | Manuals |
 | Catalogs |
| Title | Doc. nr. Edition Date | Languages | Document (Downloads) |
|---|
| Berührungsloses Sicherheitssystem CES | 076609 15 09/11 |  | 25865 KB | | Non-Contact Safety System CES | 076649 15 09/11 |  | 25794 KB | | Système de sécurité sans contact CES | 086818 15 09/11 |  | 25835 KB | | Sistema de seguridad sin contacto CES | 086819 15 09/11 |  | 26530 KB |
 | CAD data |
|
|
|
|
|