EUCHNER – More than safety.
EUCHNER – More than safety.

GMOX-PR-12DN-C16 (Order no. 103267)

AS-Interface Safety at Work safety monitor with integrated Gateway GMOx

  • One AS-i master
  • Display and pushbuttons for diagnostics and adjustment
  • Memory card for different programs
  • Adjustable time-delay
  • 16 OSSDs
GMOX-PR-12DN-C16 (Order no. 103267)

Description

Gateway to Profibus

For connection to a Profibus DP as a slave and as a master for an AS-i bus according to specification 3.0. Detection of ground shunt, double addressing and EMC problems.

Rapid setup with the display without PC. Direct display of faults with plain-text messages. Comprehensive AS-i diagnostics integrated. AS-i configuration software is available.

OSSDs (Output Signal Switching Devices), AS-i outputs

  • Two OSSDs with two redundant normally closed contacts each
  • Two OSSDs with semiconductor outputs
  • 12 additional safe AS-i outputs can be controlled

Inputs

  • 4 inputs, freely selectable

Logic functions

Programmable with AsiMon software. All safety components can be programmed with different functions as inputs. The inputs can be linked with AND or OR gates or via logic functions such as FlipFlop, switch-on delay, OFF time or pulses.

Different programs can be stored on a memory card.

AS-Interface monitor

The monitor controls two AS-i circuits with up to 62 safe slaves and up to 16 outputs.

Display and pushbuttons

The display is used to operate the gateway functionality as well as the monitor at the same time. The diagnostics and maintenance functions are considerably expanded compared to the SFM monitors. They can also be launched on the display without a PC monitor.

Incorporated security functions allow the programmed functionality to be protected and monitored.

Power supply

Type N permits connection of several GMOx devices to the same power supply unit.

Important: A connection kit must be ordered for each safety monitor. See Accessories.

Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram

Dimensional drawings

Dimensional drawings

Connection examples

Connection examples

Technical data

Approvals

EAC_RU C-DE.MO05.B.00971/20TUEV Nord_44 205 15102901_3528 6834c_UL_us_E323660_Asi Interface_83701_

Operating and display elements

Display LCD AS-i slave address indication, error messages
LED display
4 x LEDs EDM / start state of the inputs for the external device monitoring circuits: LED off: open, LED on: closed
LED AUX auxiliary power is present
LED U AS-i voltage OK
LED prj mode, configuration mode active
LED PROFIBUS master detected
LED power, power supply ON
LED AS-i active AS-i operation normal
LED config error configuration error
LED prg enable automatic slave programming possible
4 x LEDs, output circuits, state of the output circuits: LED off: open, LED on: closed
ItemExtrasColorDesignation1NumberLEDSlide-in labelNote slide-in labelSwitching elementVersion
4Pushbutton

Electrical connection values

Power consumption 9 W
Connection cross section
(2x AWG 24 to 12)
Flexible wire for cable end sleeve (2x (0.5...1.5) mm2)
for wire 2x (0.5...1.5) mm2
Response delay
Safety circuit off max. 40 ms
ASI operating current max. 300 mA
ASI voltage 30 V
ASI cycle time 150 μs 150 x (number of slaves + 2)
Outputs
NumberTypeFunctionFootnote
4Output switching elements, output circuits 1, 2, 3 and 4Relay outputs 1.13, 2.13, semiconductor outputs 1.14, 2.14, 3.14, 4.14
Rated insulation voltage Ui 500 V
Inputs
NumberTypeFunctionFootnote
4Feedback loop/startEDM1/Start1: 1.Y1; EDM2/Start2: 2.Y1; EDM3/Start3:1.Y2; EDM4/ Start4: 2.Y2(EDM: external device monitor / feedback loop)
Switch-on delay 10 s
Card slot yes (Memory card to store the configuration data)

Mechanical values and environment

Number of OSSDs 16 (4 fed out)
Number of masters 1
Mounting type Mounting rail 35mm according to DIN EN 60715TH35
Degree of protection IP20
Ambient temperature 0 ... +55 °C
Material
Housing Stainless steel
permissible shock and vibration load According to EN 61 131-2

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

Mission time 20 y
Category 4
Performance Level PL e
PFHD 5.36 x 10-9
SIL CL 3

Miscellaneous

in compliance with EN 61 000-6-2, EN 61 000-6-4, EN 62 061, IEC 61 508, EN ISO 13 849-1

Interface

Bus data protocol PROFIBUS according to EN 50 170-3
Data rate 9.6 ... 12000 kbit/s
Date interface Serial interface RS 232
Periphery Decentralized peripheral equipment mapping of the AS-i slaves as I/O process data in the PROFIBUS; complete diagnostics and configuration via PROFIBUS DP master

Downloads

Complete package

Download all important documents with a single click.

Content:

  • The operating instructions and any additions to the operating instructions or brief instructions
  • Any data sheets to supplement the operating instructions
  • The declaration of conformity
Download Complete Package (ZIP, 13,3 MB)

Single Documents

Other Documents

Ordering data

Ordernumber 103267
Item designation GMOX-PR-12DN-C16
Gross weight 0,936kg
Customs tariff number 85371098
ECLASS 27-24-31-01 Configurable control component

Technical support

Technical support
Do you have technical questions about our products, their possible use or applications? Our experts will be happy to help.

EUCHNER (UK) Ltd.
+44 114 2560123
sales(at)euchner.co.uk

EUCHNER USA Inc.
+1 315 701-0315
info(at)euchner-usa.com