EUCHNER – More than safety.
EUCHNER – More than safety.

MSC-CE-AH-FO4SO8-122705 (Sip. No. 122705)

Expansion module MSC-CE

  • Output expansion
  • 4 control inputs
  • 4 single-channel high-current semiconductor outputs (up to PL e, category 4)
  • 8 monitoring outputs
  • Compact housing with width of only 22.5mm
  • Simple diagnostics via LED displays
  • Plug-in screw terminals (expansion plug included)
MSC-CE-AH-FO4SO8-122705 (Sip. No. 122705)

Açıklama

Inputs and outputs

  • 4 control inputs for starting/restarting relay outputs or for external device monitoring (EDM)

  • 4 single-channel/2 dual-channel semiconductor outputs with up to 2 A output current (up to PL e, category 4)

  • 8 monitoring outputs programmed via the EUCHNER Safety Designer software
Three settings are available for the safe semiconductor outputs (configuration via the EUCHNER Safety Designer software):
  • 4 single-channel outputs

  • 2 dual-channel outputs

  • 1 dual-channel and 2 single-channel outputs

Scope of delivery

  • The expansion plug (order no. 121308) is included with the expansion module

Accessories

  • Plug-in screw terminals (order no. 121321) must be ordered separately

Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram
MSC: Safe control system MSC

Dimensional drawings

Dimensional drawings
1Page A
2Page B

Connection examples

Connection examples

Teknik Veriler

Approvals

EAC_RU C-DE.MO05.B.00971/20TUEV Süd München_Z10 040393 0030 Rev.01c_UL_us_E353660_UL_us_E467239

Electrical connection values

Connection cross section 0.5 ... 2.5 mm² (Screw terminal)
Outputs
NumberTypeFunctionFootnote
2Semiconductor outputs, p-switching, short circuit-proofSafety outputs (OSSD)(usable as 4 single-channel OSSDs)
8Semiconductor outputs, p-switchingMonitoring outputs, programmable(according to EN 61131-2)
Output voltage
Safety outputs (OSSD) UB-0.75 ... UB V DC HIGH
Safety outputs (OSSD) 0 ... 2 V DC LOW
Output current
Safety outputs (OSSD) 0 ... 2000 mA
Monitoring outputs, programmable max. 100 mA
Operating voltage DC
UB 24 V DC -20% ... +20% PELV (according to EN 60204-1)
Inputs
NumberTypeFunctionFootnote
2Semiconductor outputs, p-switchingfor node selection("Type 2" according to EN 61131-2)
4Semiconductor outputs, p-switchingFeedback loop monitoring (EDM)(according to EN 61131-2)
Input voltage
Test pulse duration
Safety outputs (OSSD) 0.1 ms
Test outputs 0.2 ms
Test pulse interval 600 ms
Overvoltage category according to IEC EN 60664-1 II
Power dissipation max. 4 W
Degree of contamination according to EN 60664-1 2

Mechanical values and environment

Dimensions 108 x 22.5 x 114.5 (Including screw terminals)
Connection type Plug-in screw terminal (Terminals not included)
Storage temperature -20 ... +85 °C
Cable length max. 100 m (with length above 50 m, cross-section>use 1 mm²)
Atmospheric humidity 10 ... 95 % rH
Mounting type 35 mm mounting rail (according to EN 60715)
Degree of protection IP20
Ambient temperature -10 ... +55 °C
Material
Housing Polyamide

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

Mission time 20 y
Category 4
Performance Level PL e
PFHD 8.56 E-09 1/h (according to IEC 61508:2010)

İndirme

Komple paket

Tüm önemli belgeleri tek bir tıklama ile indirin.

İçerik:

  • Kullanım talimatları ve kullanım talimatlarına veya kısa talimatlara yapılan tüm eklemeler
  • Kullanım talimatlarını tamamlayan tüm veri sayfaları
  • Uygunluk beyanı
Paketin tamamını indirin (ZIP, 57,9 MB)

Tek Belgeler

Diğer Belgeler

Sipariş verileri

Sip. No. 122705
Makale adı MSC-CE-AH-FO4SO8-122705
Ağırlık 0,213kg
Gümrük sınıfı 85364110

Teknik Destek

Teknik Destek
Do you have technical questions about our products, their possible use or applications? Our experts will be happy to help.

EUCHNER End. Emn. Tek. Ltd. Sti.
+90 216 521-1000
info(at)euchner.com.tr